- RS Stock No.:
- 188-3546
- Mfr. Part No.:
- ELRM44V-30 12-125V DC
- Manufacturer:
- Broyce Control
- RS Stock No.:
- 188-3546
- Mfr. Part No.:
- ELRM44V-30 12-125V DC
- Manufacturer:
- Broyce Control
Technical data sheets
Legislation and Compliance
- COO (Country of Origin):
- GB
Product Details
This product is used in conjunction with an external Core Balance Current Transformer (CBCT) and will detect residual sinusoidal alternating and pulsating direct currents. An adjustable trip level and time delay allows the product to be set according to the type of installation to be protected. When the level of leakage current being monitored exceeds the set trip level, the unit will trip. Typically, the product is used in conjunction with an external switching device (i.e. contactor, shunt trip). An auxiliary supply is required to power this product.
Type A - Earth Leakage Relay
Selectable Trip level (0.03 - 30A) and Time delay (0 - 10s)
Local (and optional remote) Test/Reset buttons
Isolated Auxiliary supply
1 x SPDT/1 x SPNO Relay outputs
44mm wide, DIN Rail mount
Selectable Trip level (0.03 - 30A) and Time delay (0 - 10s)
Local (and optional remote) Test/Reset buttons
Isolated Auxiliary supply
1 x SPDT/1 x SPNO Relay outputs
44mm wide, DIN Rail mount
Specifications
Attribute | Value |
---|---|
Frequency Range | 50 Hz, 60 Hz, 400Hz |
Leakage Range | 30A |
Output | SPDT, SPNO |
Protection Class | Type A |
Test Function | Remote |
Dimensions | 44 x 63.5 x 85mm |
Weight | (AC Power Supplies)190 g, (DC Power Supplies)110g |