Megger LTW425 Loop Impedance & RCD Combined Tester, Loop Impedance Test Type 2 Wire 440V, RCD Test Type AC Selective

  • RS Stock No. 237-883
  • Mfr. Part No. LTW425
  • Manufacturer Megger
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
COO (Country of Origin): GB
Product Details

LTW425

The Megger LTW425 two wire earth loop tester verifies the loop impedance of a live electrical circuit, ie without the need to disconnect the electrical supply. Offers a high resolution 2-wire loop testing solution that does not trip 30 mA RCDs and can be used on a wide range of voltages.

High resolution (0.001Ω) 2 wire testing + maxZ + (R1+R2)
Backlit display
2 wire loop tests: Phase to Earth, Phase to Neutral or Phase to Phase
3 phase circuits with RCD protection can be tested
Tests radial circuits where the circuit does not return to the origin, even where only a phase and neutral contacts are available.
10 second non trip loop test time with Auto test extension up to a further 10 seconds if noise is detected, to improve the accuracy of the test
High current loop testing for supplies that do not have an RCD fitted
AUTO START will start the loop test running as soon as the test leads are connected; No need to press the test button means much safer testing
PFC Display up to 40kA
Voltage and frequency measurement
110 Vac systems including 110V centre tap to earth (55 V phase to earth) can be tested on the secondary winding.
IP54 Weatherproof case
Optional 10A fused 2 wired test leads and crocodile clip set
Complies with IEC61010-1 300V CATIV safety standard and meets EN61557

Note

RS is an authorised Megger distributor. Purchased though RS this product is eligible for the Megger extended 3 Year warranty

Supplied with

Test lead set with crocodile clips, mains socket test lead, 8 AA alkaline batteries, hard carry case and instructions.

Specifications
Attribute Value
Calibrated RSCAL
Loop Impedance Test Type 2 Wire
Maximum Voltage Measurement 440V
RCD Test Type AC Selective
Best Loop Test Accuracy ±10%
RCD Test Current 4A
Non-Trip Loop Test Yes
Safety Category CAT IV 300 V, IEC 61010
Display Type LCD
Battery Life 2000 Tests
Battery Type AA
Power Source Battery
Dimensions 203 x 148 x 78mm
Weight 1kg
Safety Category Voltage 300V
Safety Category Level CAT IV
Model Number p LTW425
Height 78mm
Minimum Operating Temperature -10°C
Length 203mm
Width 148mm
Maximum Operating Temperature +50°C
2 In stock, please allow up to 5 working days for delivery
Unit of sale: Each
756.05
(exc. VAT)
929.94
(inc. VAT)
units
Per unit
1 +
€756.05
Related Products
DET24C is a clamp-on ground resistance tester that ...
Description:
DET24C is a clamp-on ground resistance tester that set new standards in terms of access, performance, features, simplicity of operation and safety The units are designed with flat core ends to prevent dirt build-up, ensuring measurement integrity and improved reliability ...
TESTRANSFO2 is a small, hand held device which ...
Description:
TESTRANSFO2 is a small, hand held device which is used to check the functionality of a tri-phased transformer disconnected from the network Usable on all distribution transformers. It automatically performs a sequence of tests taking only two min to confirm ...
A portable digital flash tester incorporating an electronically ...
Description:
A portable digital flash tester incorporating an electronically controlled variable test voltage and safety flash probe, suitable for testing to 17th Edition Regulations (BS7671) Selectable 120/240V, 50/60Hz operation Incorporates a solid state regulator to give stepless voltage adjustment, with safety ...
The DT-500 checks insulation resistance for systems or ...
Description:
The DT-500 checks insulation resistance for systems or devicesA 500 V measuring voltage delivered by the device is used to perform this check (in compliance with NF C15-100).Phase / neutral shunt function.Battery-saving function.Live voltage indicator and battery status indicator.Belt clip ...