Megger LTW425 Loop Impedance & RCD Combined Tester, Loop Impedance Test Type 2 Wire 440V, RCD Test Type AC Selective

  • RS Stock No. 238-145
  • Mfr. Part No. LTW425
  • Manufacturer Megger
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
COO (Country of Origin): GB
Product Details

LTW425

The Megger LTW425 two wire earth loop tester verifies the loop impedance of a live electrical circuit, ie without the need to disconnect the electrical supply. Offers a high resolution 2-wire loop testing solution that does not trip 30 mA RCDs and can be used on a wide range of voltages.

High resolution (0.001Ω) 2 wire testing + maxZ + (R1+R2)
Backlit display
2 wire loop tests: Phase to Earth, Phase to Neutral or Phase to Phase
3 phase circuits with RCD protection can be tested
Tests radial circuits where the circuit does not return to the origin, even where only a phase and neutral contacts are available.
10 second non trip loop test time with Auto test extension up to a further 10 seconds if noise is detected, to improve the accuracy of the test
High current loop testing for supplies that do not have an RCD fitted
AUTO START will start the loop test running as soon as the test leads are connected; No need to press the test button means much safer testing
PFC Display up to 40kA
Voltage and frequency measurement
110 Vac systems including 110V centre tap to earth (55 V phase to earth) can be tested on the secondary winding.
IP54 Weatherproof case
Optional 10A fused 2 wired test leads and crocodile clip set
Complies with IEC61010-1 300V CATIV safety standard and meets EN61557

Note

RS is an authorised Megger distributor. Purchased though RS this product is eligible for the Megger extended 3 Year warranty

Supplied with

Test lead set with crocodile clips, mains socket test lead, 8 AA alkaline batteries, hard carry case and instructions.

Specifications
Attribute Value
Loop Impedance Test Type 2 Wire
Calibrated UKAS
Maximum Voltage Measurement 440V
RCD Test Type AC Selective
Best Loop Test Accuracy ±10%
RCD Test Current 4A
Non-Trip Loop Test Yes
Safety Category CAT IV 300 V, IEC 61010
Display Type LCD
Battery Life 2000 Tests
Battery Type AA
Power Source Battery
Dimensions 203 x 148 x 78mm
Weight 1kg
Maximum Operating Temperature +50°C
Safety Category Voltage 300V
Length 203mm
Safety Category Level CAT IV
Width 148mm
Height 78mm
Minimum Operating Temperature -10°C
Model Number p LTW425
4 In stock, please allow up to 5 working days for delivery
Unit of sale: Each
771.05
(exc. VAT)
948.39
(inc. VAT)
units
Per unit
1 +
€771.05
Related Products
In their rugged, sealed housing, the CA 6460 ...
Description:
In their rugged, sealed housing, the CA 6460 and CA 6462 are easy to use and are designed specifically for operation in the fieldThe CA 6460 and CA 6462 help to establish a fast and accurate diagnosis with optimum comfort ...
Single-phase measuring adapter for the PROFiTEST INTRO, earthing ...
Description:
Single-phase measuring adapter for the PROFiTEST INTRO, earthing contact plugs to three 4 mm safety plugs (black, blue, yellow-green), 230 V AC, touch-guarded, measuring category: CAT III, 300 V, 16 A
Single-phase, measuring adapter for the PROFiTEST INTRO, earthing ...
Description:
Single-phase, measuring adapter for the PROFiTEST INTRO, earthing contact plugs to three 4 mm safety plugs (black, blue, yellow-green), 230 V AC, touch-guarded, measuring category: CAT III, 300 V, 16 A
The PROFITEST MXTRA Starter Pack Kit consists of ...
Description:
The PROFITEST MXTRA Starter Pack Kit consists of the M520P test insrument along with a VARIO plug adapter set, F2000 universal carrying pouch, rechargeable battery pack and battery charger Loop and line impedance measurement Measurement of insulation resistance using nominal ...