Schneider Electric Acti 9 iC60H MCB Mini Circuit Breaker 1P, 10 A, 10 KA, Curve B

Technical data sheets
Legislation and Compliance
RoHS Certificate of Compliance
COO (Country of Origin): BG
Product Details

Schneider Electric | Acti9 iC60H | Mini Circuit Breakers

The Acti9 series of MCBs by Schneider Electric provides excellent circuit protection particularly in combating short circuits and overload currents. These MCBs are rigorously tested by Schneider and are compliant with standards such as IEC/EN 60898 & 60947-2. These types of MCBs are typically used in industrial or commercial buildings and can work extremely well in polluted environments.

Features and benefits:

• Easy to install these consumer units, single clip on to Din Rail, compact in nature making wiring easier and simplifying your circuit system. Ergonomically designed with robust connections. IP20B terminal shutters.

• Schneider 'VisiSafe' for safer operation and maintenance work on electrical circuits. Absolute safety of circuit protection guaranteed.

• Schneider 'VisiTrip' for easier fault detection in the MCB outgoers. This can help reduce intervention time greatly, protecting the device before any further electrical problems occur.

• 1P (number of protected poles).

• Nominal currents ranging from 1 to 63 Amps.

• Full compatibility with Acti 9 RCDs and MCCBs.

• Operating voltage up to 440 V ac, insulation voltage 500 V.

• Additional add-on earth leakage protection devices are available. This offers you better continuity of service.

• Schneider Green Premium classed product.

Protection ratings & Safety features (See datasheet for further details) -

• IP20 conforming to IEC 60529. Protection against solid objects up to 12mm e.g. fingers, small tools.

• Pollution degree level of 3 conforming to EN/IEC 60947-2.

• EN/IEC 60947-2 & EN/IEC 60898-1.

• Operating temperature (for operation) -35 to 70 ° C.

• Padlockable, providing extra protection.

Applications -

• DC current circuit protection / Motor circuit protection.

• Polluted environments/networks.

• Any circuit types within industrial/commercial buildings.

Q&A: What is the differences in the Tripping Curves B, C, and D?

A: Curve B: Tripping: 3 to 5 times the rated current.
Applications: protection of generators, persons, very long cables
Curve C: Tripping: 5 to 10 times the rated current
Applications: protection of circuits and general applications
Curve D: Tripping: 10 to 14 times the rated current
Applications: protection of high surge circuits, welders, transformers and motors

Note

The Acti9 come in either Curve B , C or D. Please refer to specifications for specific type.

A9F53110 Schneider Electric MCB

This model has tripping curve type B that trips instantly at a rate of 3 to 5 times the rated current 1 pole breaker and a breaking capacity of 10 kA.

Specifications
Attribute Value
Range Acti 9
Series iC60H
Number of Poles 1
Current Rating 10 A
Tripping Characteristics Type B
Rated AC Voltage 12 → 60 V, 100 → 133 V, 220 → 240 V
Rated DC Voltage 12 → 48 V, 72 V
Mounting Style DIN Rail
Breaking Capacity 10 kA
Length 85mm
Width 18mm
Depth 78.5mm
Reset Actuator Type Rocker
Tripping Mechanism Thermal-Magnetic
Circuit Breaker Type MCB
Terminal Contact Type Screw
5 Within 1 working day(s) (IE stock)
241 Within 2 working day(s) (EU stock)
Unit of sale: Each
16.14
(exc. VAT)
19.85
(inc. VAT)
units
Per unit
1 - 9
€16.14
10 - 14
€15.32
15 +
€14.81
Related Products
The Schneider Electric MCB is a 4 pole ...
Description:
The Schneider Electric MCB is a 4 pole compact NSX moulded case circuit breaker upto 630A Its current rating is 100A with type D tripping characteristics. The tripping mechanism is thermal magnetic. • 690V rated AC voltage• Breaking capacity of ...
C60H series are a high performance range of ...
Description:
C60H series are a high performance range of MCBs for direct current networks These are designed for demanding installations to ensure maximum continuity of service Tripping Curve C. Reliability: guaranteed breaking of DC current for best anti-fire protection. The C60HDC ...
B, C and D curve Visisafe green strip ...
Description:
B, C and D curve Visisafe green strip indicates and guarantees the safe position of contacts VisiTrip red window on the front face indicates fault tripping allowing fast diagnosis, resolution, and re-closing loads for easier building management and reduced downtime ...
Acti 9 Schneider iC60N series multi-standard circuit breakers ...
Description:
Acti 9 Schneider iC60N series multi-standard circuit breakers combine circuit protection against short circuit currents and circuit protection against overload currents it also protects people against indirect contact with TN and IT neutral systems Fully compliant with standards IEC/EN 60898 ...