Jumo Capillary Thermostat, 300 °C Max, Automatic Reset, 10 A, Surface Mount

Subtotal (1 unit)*

€408.71

(exc. VAT)

€502.71

(inc. VAT)

Add to Basket
Select or type quantity
Temporarily out of stock
  • Shipping from 26 March 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +€408.71

*price indicative

RS Stock No.:
278-889
Mfr. Part No.:
603021/70-2-064-00-1000-40-10-00-00-000-00-6/574
Manufacturer:
Jumo
Find similar products by selecting one or more attributes.
Select all

Brand

Jumo

Product Type

Thermostat

Minimum Operating Temperature

50°C

Maximum Operating Temperature

300°C

Thermostat Type

Capillary

Contact AC Voltage

230V ac

Contact Current

10A

Hazardous Area Certification

No

Standards/Approvals

DIN EN 14597, DGRL, RoHS, EAC

Series

603021

Reset Type

Automatic

Mount Type

Surface Mount

COO (Country of Origin):
DE
The Jumo 1 Pole Mechanical Surface Mounting Thermostat is very robust and can also be used in rough conditions. The measuring system used operates on the fluid expansion principle and can be used without any problems up to a maximum permissible probe temperature of 345°C. A decisive advantage is that no additional auxiliary energy is necessary for temperature measurement. The electrical connection is made directly to the installed microswitch via screw terminals, which can directly switch a maximum permissible switching capacity of AC 230 V / 10 A. The safety temperature limiter can be used very flexibly and is used in heating, air conditioning and ventilation technology as well as in the plastics industry, in apparatus and mechanical engineering and in furnace construction, in district heating transfer stations and for temperature monitoring in laboratories and climatic chambers.

Shock resistant case with high quality plastic cover

Aluminium die cast lower part

Approved according to DIN EN 14597 and an EAC approval

Stainless steel sensor and 6 mm diameter with 55 mm probe length

Copper capillary and flexible with 5 mm bending radius

Max. ambient temp is 80 °C (IP54)

Adjustable switch off temp with screwdriver

Circuit opens if temp exceeds limit and signal contact closes

Micro switch locked can be manually unlocked after temp drops 10%

+0/-5% accuracy in upper third of scale

Circuit permanently opened if system is damaged

Neutral switching contact if system fails