Unipower 130 A Motor Load Monitor, 24 V dc, -15 → +50 °C

  • RS Stock No. 793-4115
  • Mfr. Part No. APM382
  • Manufacturer Unipower
Technical data sheets
Legislation and Compliance
RoHS Certificate of Compliance
COO (Country of Origin): DK
Product Details

APM382 - Analogue Load Monitor

The APM382 is a combined electronic power measurement transducer and load monitor that measures power in kW on 3-phased asymmetric loads, including frequency inverter.

Measures after frequency inverters; PWM 10Hz - 1kHz
10 current measuring ranges up to 80A internally
Digital scaling of the selected range (Zoom)
Programmable filter function (analogue and digital)
2 independent alarm limits plus dP/dt (shock load) alarm
Alarm inhibit inputs and external reset input
0(4)-20mA and 0(2)-10V analogue outputs
Galvanic isolation between mains net and I/O
Setup of parameters via PC with software 382Mon
Optocoupled alarm outputs
An external display (DCU D382; Stock-no.: 793-4124) can be connect

Unipower Motor Protection

Specifications
Attribute Value
Motor Protection Component Load Monitor
Number of Inputs 6
Output 2
Sensing Type Current Transformer
Supply Voltage 24 V dc
Current Rating 130 A
Overall Length 102mm
Overall Width 86mm
Overall Depth 58mm
Minimum Operating Temperature -15°C
Maximum Operating Temperature +50°C
Size D 58 x W 102 x H 86mm
Enclosure Type Lexan UL94V-0 (Upper), Noryl UL94V-0 (Lower)
Series APM
2 In stock for delivery within 2 working days
Unit of sale: Each
801.93
(exc. VAT)
986.37
(inc. VAT)
units
Per unit
1 +
€801.93
Related Products
The 3RV10 current limiting motor starter protector is ...
Description:
The 3RV10 current limiting motor starter protector is commonly known as a motor protection switch, as they are used for switching and protecting induction motors Seimens 3RV Manual Motor Starters are optimized for load feeders. The motor circuit breakers are ...
The Omron motor condition monitoring device quantifies the ...
Description:
The Omron motor condition monitoring device quantifies the status of the 3-phase induction motor and pump It has a current rating of 600A and voltage rating of 24VAC/DC. The default alarm output threshold is already set. You can customize the ...
The load power monitor achieves effective protection for ...
Description:
The load power monitor achieves effective protection for three-phase motors in critical applications, guarding against nuisance trips because of voltage fluctuations,Reliable detection of overload or underload operating conditions is achieved by measurement of this true power. Independent settings for power ...
Can be used with all motors equipped with ...
Description:
Can be used with all motors equipped with PTC thermistor probes It monitors windings temperature and ensures that the rated operating value is not exceeded, therefore guarding against faults which are often the cause of premature ageing. They can also ...