Fluke 1550C Insulation Tester, 250 V Min, 5000 V Max CAT IV, CAT III

Subtotal (1 unit)*

€6,375.00

(exc. VAT)

€7,841.25

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • Plus 4 unit(s) shipping from 23 March 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +€6,375.00

*price indicative

RS Stock No.:
705-1957
Mfr. Part No.:
FLUKE 1550C
Manufacturer:
Fluke
Find similar products by selecting one or more attributes.
Select all

Brand

Fluke

Model Number

1550C

Product Type

Insulation Tester

Tester Type

Insulation Tester

Maximum Test Voltage

5000V

Minimum Test Voltage

250V

Display Type

LCD

Test Current

2000000nA

Battery Type

Rechargeable Lead Acid (Yuasa NP2.8-12)

Power Source

Battery

Minimum Operating Temperature

-20°C

Maximum Operating Temperature

50°C

Safety Category Level

CAT IV, CAT III

Safety Category Voltage

1000V

Standards/Approvals

CE, CSA

Length

277mm

Height

160mm

Weight

3.7kg

COO (Country of Origin):
US

Fluke Insulation Tester, 5 MΩ to 1 TΩ Insulation Testing Resistance, 5000V Maximum Test Voltage - FLUKE 1550C


This insulation tester is a portable instrument for assessing insulation resistance on high-voltage plant and machinery. It is designed for field maintenance and diagnostic work on switchgear, motors, generators and cables, enabling technicians in automation, electrical, electronics and mechanical environments to perform timed, ramp and leakage tests at controlled DC voltages.

Features & Benefits


• Selectable test voltages from 250V to 5000V for varied assets
• Insulation resistance range to 1TΩ for high‑resistance detection
• Test current capability up to 2,000,000nA for accurate leakage readings
• Rechargeable lead‑acid power for extended field use between charges
• CAT IV 600V CAT III 1000V rating for enhanced on-site safety
• Large LCD with analogue bar graph for clear trend visualisation

Applications


• Suitable for preventive maintenance of switchgear and transformers
• Ideal for commissioning and fault diagnosis on medium‑voltage motors
• Used for insulation assessment on long cable runs and accessories
• Can be used for generator insulation health trending and reporting

What power source does it use for mobile operation


It runs from a 12V lead‑acid rechargeable battery, enabling multiple test cycles before recharging.

How does it handle capacitance and discharge requirements


It measures capacitance up to 15.00μF and provides controlled charge/discharge rates for capacitive loads.

How are results recorded and shared on site


Measurements can be stored locally and transmitted via an infrared connector to a mobile app for wireless logging and trending.

What environmental limits affect on-site performance


Operable between -20°C and 50°C with humidity limits that reduce from 80% at 31°C to 50% at 50°C.

What certifications and protection levels does it meet


It carries CE and CSA approvals and an IP40 enclosure rating suitable for industrial environments.

Contents

1550C 705-1957
Test cables with alligator clips (red, black, green)
AC poer cord
Soft carrying case
English manual
Quick reference card

Software FVF-884X, FLUKEVIEW FORMS - BASIC FOR 8845/8846