Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Fluke | |
| Maximum Resistance Measurement | 19.99kΩ | |
| Product Type | Earth Tester Kit | |
| Accuracy | ±2 % rdg + 3 Digits | |
| Display Type | LCD | |
| Measurement Type | Ground Resistance | |
| Battery Life | 3000h | |
| Battery Type | AA Alkaline | |
| Power Source | Battery | |
| Weight | 1.1kg | |
| Height | 133mm | |
| Includes | Batteries, Cable Reel, Carrying Case, User Manual | |
| Length | 187mm | |
| Standards/Approvals | IEC61010-1 | |
| Maximum Operating Temperature | +50°C | |
| Minimum Operating Temperature | -10°C | |
| Width | 250mm | |
| Safety Category Level | CAT II | |
| Model Number | 1623-2 | |
| Safety Category Voltage | 300V | |
| Select all | ||
|---|---|---|
Brand Fluke | ||
Maximum Resistance Measurement 19.99kΩ | ||
Product Type Earth Tester Kit | ||
Accuracy ±2 % rdg + 3 Digits | ||
Display Type LCD | ||
Measurement Type Ground Resistance | ||
Battery Life 3000h | ||
Battery Type AA Alkaline | ||
Power Source Battery | ||
Weight 1.1kg | ||
Height 133mm | ||
Includes Batteries, Cable Reel, Carrying Case, User Manual | ||
Length 187mm | ||
Standards/Approvals IEC61010-1 | ||
Maximum Operating Temperature +50°C | ||
Minimum Operating Temperature -10°C | ||
Width 250mm | ||
Safety Category Level CAT II | ||
Model Number 1623-2 | ||
Safety Category Voltage 300V | ||
RoHS Status: Exempt
Fluke Earth Tester Kit, 19.99kΩ Maximum Resistance Measurement, ±2% rdg + 3 Digits Accuracy - FLUKE-1623-2 KIT
This earth tester kit is a battery-powered instrument for measuring ground and earth loop resistance in utility, industrial and maintenance settings. It performs 3- and 4-pole fall-of-potential and soil resistivity tests, selective and stakeless clamp-based checks, and stores results for USB download. The unit is designed for outdoor use and portable field work, supplied with accessories for comprehensive site testing.
Features & Benefits
• Measures up to 19.99kΩ for broad resistance range
• LCD display with 1999-digit visibility for clear readings
• Internal memory holds up to 1500 records for data capture
• IP56 protection for use in dusty or wet conditions
• Battery life greater than 3000 measurements with AA alkaline cells
• Stakeless testing with two clamps to save setup time
• LCD display with 1999-digit visibility for clear readings
• Internal memory holds up to 1500 records for data capture
• IP56 protection for use in dusty or wet conditions
• Battery life greater than 3000 measurements with AA alkaline cells
• Stakeless testing with two clamps to save setup time
**Applications**
• Suitable for fault-to-earth impedance assessment in substations
• Ideal for site surveys where stake placement is impractical
• Used for soil resistivity mapping during earthing design
• Can be used for selective testing of individual earthing rods
• Suitable for routine maintenance checks in industrial plants
• Ideal for site surveys where stake placement is impractical
• Used for soil resistivity mapping during earthing design
• Can be used for selective testing of individual earthing rods
• Suitable for routine maintenance checks in industrial plants
How does the instrument handle interference from nearby electrical systems?
It includes frequency selection and automatic frequency control to identify and avoid interfering signals and minimise measurement error.
What safety classification applies when working near live equipment?
The instrument meets CAT II 300V limits for external voltage conditions and provides double or reinforced insulation with measurement inhibited above safe thresholds.
What data transfer options are available for job reporting?
Test results are stored in internal memory and can be exported via the USB port for analysis and Record keeping.
How is stakeless measurement performed without disconnecting the earthing system?
One clamp injects a known AC voltage while a second clamp measures current, allowing closed-loop resistance determination without removing bonds.
Supplied with
1623-2 GEO Earth Ground Tester, user manual, batteries, quick reference guide, USB cable, 2 clamps, C1620 carrying case, 4 earth ground stakes and 3 cable reels
Related links
- Fluke 1623-2 CAT II 300V RSCAL
- Fluke 1623 Earth Tester, 20 kΩ CAT II 300V
- Fluke 1623 Earth Tester, 20 kΩ CAT II 300V UKAS
- Fluke 1623 Earth Tester, 20 kΩ CAT II 300V RSCAL
- Fluke 1625 CAT II 300V RSCAL
- Fluke 1625 CAT II 300V
- Fluke 1625-2 Earth Tester, 300 kΩ CAT II 300V
- Fluke 1625-2 Earth Tester, 300 kΩ CAT II 300V RSCAL